- New or better definitions were added:
- Jockey pumps or sometimes referred to as pressure maintenance pumps
(PMP)
- Packaged fire pumps or prepackaged fire pump units
- The return of Chapter 4 on fire pumps in high rise buildings was added
- Information pertaining to jockey pumps and their pump sizing is provided
- In Chapter 5 a new section was added on prepackaged fire pumps
- FM approved flexible couplings are now available and are now required
to be FM approved
- Chapter 10 on Electric Driven Control Units removed the section on limited
service controllers
- Chapter 11 on Diesel Engine Drives was completely reworked as follows:
- The EPA standards have required cleaner emissions over the last
few years and will require all diesel engines to meet very stringent
emission standards
- Electronic Controlled Modules (ECM's) are now required for fuel
management
- In the past two manually operated ECM's were required now two automatic
ECM's need to be provided on all diesel driven engines no matter when
the engine was installed
- A new Contractor Material Test Certificate (CMTC) designed specifically
for fire/booster pumps was added
Jockey Pumps
Jockey pumps are sized and provided to replenish the fire protection system
pressure due to the allowable leakage and normal drops in pressure or as
NFPA 20 states "Shall have rated capacities not less than normal leakage".
How is anyone to know what the normal leakage rate is?
NFPA 20 does not intend to leave a leaking system. You should do a dry
joint test at the required test pressures. These allowances give an indication
of the loss of water that will take place over time due to earth movement,
traffic, or soil settling.
NFPA 20 goes on to state that the maximum leakage per 100 joints is two
quarts per hour, which translates into an estimated loss of approximately
14 gallons per hour. You also must allow for incidental leaking or use within
the thousands of feet of pipe inside the facility. The standard requires
the water and the pressure should be replenished within ten minutes. Taking
the system pressure into account, your choice of pumps will be sized much
larger than the water usage. High-pressure requirements in some sprinkler
systems may require the pressure to be at 165-psi static pressure. That
means the jockey pump will be required to deliver 20 gpm or more at 165
psi to meet the requirements.
What is Reliable Power?
The past editions of the NFPA 20 indicated that the power source to fire
pumps must be reliable. So what was considered reliable?
You will not find a definition of a reliable power source within the NFPA
20 standard, past or present. The lack of information of how to determine
reliability put installers, owners, and Authority Having Jurisdictions (AHJ's)
in situation that was up to interpretation. Some installations have resorted
to installing generators or diesel driven fire pumps to resolve the reliability
issue and this adds significant cost to the project and may make the cost
benefit of an electrical pump versus a diesel pump a non-factor. Some jurisdictions
went as far as requiring a backup power supply when an electric driven fire
pump was installed.
NFPA 20 intent is that if a single reliable power source is available and
used to drive the electric pump motor, nothing more is required such as
an on-site generator. Fortunately, the annex Section A.9.3.2 was expanded
in the 2007 edition and included in the 2010 edition of NFPA 20 on how to
determine the reliability of the power supply to a fire pump by evaluating
four different characteristics. If any of the following cannot be met than
a back up reliable power supply is necessary.